Parameter list
Parameters
1-229
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the speed for the identification of the moment of inertia and the vibration test.
Induction motor:
The percentage value is referred to p0310 (rated motor frequency).
Synchronous motor:
The percentage value is referred to the minimum from p0310 (rated motor frequency) and p1082 (maximum
speed).
Dependency:
Refer to: p0310, p1959
Refer to: A07984, A07985
Note:
In order to calculate the inertia, sudden speed changes are carried-out - the specified value corresponds to the
lower speed setpoint. This value is increased by 10 % for the upper speed value.
Description:
Sets the dynamic response factor for speed controller optimization.
Dependency:
Refer to: p1959
Refer to: A07985
Description:
Displays the dynamic factor which is actually achieved for the vibration test
Dependency:
Refer to: p1959, p1967
Refer to: A07985
Note:
This dynamics factor only refers to the control mode of the speed controller set in p1960.
Description:
Displays the identified moment of inertia of the drive.
After it has been determined, the value is transferred to p0341, p0342.
Dependency:
Refer to: p0341, p0342, p1959
Refer to: A07984
p1965
Speed controller optimization speed / n_opt speed
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Motor identification
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
10 [%]
75 [%]
50 [%]
p1967
Speed controller optimization dynamic factor / n_opt dyn_factor
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Motor identification
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
1 [%]
400 [%]
100 [%]
r1968
Speed controller optimization dynamic factor actual / n_opt dyn_fact act
VECTOR (n/M)
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Motor identification
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
r1969
Speed controller, identified optimization inertia / n_opt M_inert iden
VECTOR (n/M)
Can be changed:
-
Access level:
4
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Motor identification
Units group:
INERTIA
Unit selection:
-
Min Max
Factory
setting
- [kgm²]
- [kgm²]
- [kgm²]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...