14. USING A DIRECT DRIVE MOTOR
14 - 8
(1) Selection example of wires
POINT
Wires indicated in this section are separated wires.
Selection condition of wire size is as follows.
Construction condition: One wire is constructed in the air.
Wire length: 30m or less
Use the 600V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire). The following table shows
the wire size selection example.
Table 14.1 Wire size selection example (HIV wire)
Wire [mm
2
] (Note 1)
Servo amplifier
1) L
1
/L
2
/L
3
/
(Note 3)
2) L
11
/L
21
3) U/V/W/
(Note 2, 3)
4) P /C 5)
P /D
MR-J3W-22B
MR-J3W-44B
MR-J3W-77B
2 (AWG14)
MR-J3W-1010B
Note 1. Wires are selected based on the highest rated current among combining servo motors.
2. The wire size is for extension cables used when the wiring length is longer than 10m.
3. Use the crimp terminal specified as below for the PE terminal of the servo amplifier.
Crimp terminal: FVD2-4
Tool: YNT-1614
Manufacturer: Japan Solderless Terminals
Tightening torque: 1.2N m