5. PARAMETERS
5 - 14
No.
Symbol
Name and function
Setting
Factory
setting
Unit
Setting
range
PB17
Automatic setting parameter
The value of this parameter is set according to a set value of parameter
No.PB06 (Load to motor inertia moment ratio).
PB18
LPF
Low-pass filter setting
Set the low-pass filter.
Setting parameter No.PB23 (low-pass filter selection) to "
0 " automatically
changes this parameter.
When parameter No.PB23 is set to "
1 ", this parameter can be set
manually.
Each
axis
3141 rad/s 100
to
9000
PB19
VRF1 Vibration suppression control vibration frequency setting
This parameter cannot be used in the speed control mode.
Set the vibration frequency for vibration suppression control to suppress low-
frequency machine vibration, such as enclosure vibration. (Refer to section 7.3.)
When parameter No.PB02 is set to "
2", this parameter can be set
manually.
Each
axis
100.0 Hz 0.1
to
100.0
PB20
VRF2 Vibration suppression control resonance frequency setting
This parameter cannot be used in the speed control mode.
Set the resonance frequency for vibration suppression control to suppress low-
frequency machine vibration, such as enclosure vibration. (Refer to section 7.3.)
When parameter No.PB02 is set to "
2", this parameter can be set
manually.
Each
axis
100.0 Hz 0.1
to
100.0
PB21
This parameter is not used. Do not change the value.
0.00
PB22
0.00
PB23 VFBF Low-pass filter selection
Select the low-pass filter.
Low-pass filter selection
0: Automatic setting
1: Manual setting (parameter No.PB18 setting)
0 0
0
When automatic setting has been selected, select the filter that has the band
width close to the one calculated with
VG2 10
1 + GD2
[rad/s]
Each
axis
0000h Refer
to
Name
and
function
column.
PB24
*MVS Slight vibration suppression control selection
Select the slight vibration suppression control and PI-PID change.
When parameter No.PA08 (Auto tuning mode) is set to "
3", the slight
vibration suppression control is enabled. (Slight vibration suppression control
cannot be used in the speed control mode.)
Slight vibration suppression control selection
0: Invalid
1: Valid
0 0
PI-PID control switch over selection
0: PI control is valid. (Switching to PID
control is possible with instructions of
controller.)
3: PID control is always valid.
Each
axis
0000h Refer
to
Name
and
function
column.
PB25
This parameter is not used. Do not change the value.
0000h
Содержание MELSERVO-J3W Series
Страница 17: ...8 MEMO ...
Страница 27: ...1 FUNCTIONS AND CONFIGURATION 1 10 MEMO ...
Страница 87: ...4 STARTUP 4 14 MEMO ...
Страница 117: ...5 PARAMETERS 5 30 MEMO ...
Страница 129: ...6 GENERAL GAIN ADJUSTMENT 6 12 MEMO ...
Страница 185: ...10 CHARACTERISTICS 10 8 MEMO ...
Страница 241: ...11 OPTIONS AND AUXILIARY EQUIPMENT 11 56 MEMO ...
Страница 274: ...13 USING A LINEAR SERVO MOTOR 13 25 1 2 3 4 ...