13. USING A LINEAR SERVO MOTOR
13 - 54
(2) List of details
No. Symbol
Name
Setting
Factory
setting
Unit
Setting
range
PS01 **LIT1 Linear function selection 1
The magnetic pole detection setting, the stop interval setting at home position
return, the valid/invalid setting of the linear servo motor thermistor can be
selected. (Refer to section 13.5.2.)
Stop interval setting at home position return
The stop interval for the dog method home position return is
set.
Setting
value
Stop interval
[pulse]
0
8192
1
131072
2
262144
3
1048576
4
4194304
5
16777216
6
67108864
Linear servo motor magnetic pole detection setting
0: Magnetic pole detection invalid (This setting is valid only
with absolute position Iinear encoder.)
1: Magnetic pole always valid
0
Linear servo motor thermistor valid/invalid setting
0: Valid
1: Invalid
When the linear servo motor without thermistor is used, this
setting is invalid.
Each
axis
0301h Refer
to
name
and
function
column.
PS02
**LIM Linear encoder resolution setting Numerator
Set the linear encoder resolution in 1 m unit. (Refer to section 13.5.1 (4).)
Set the numerator for parameter No.PS02.
Linear encoder resolution ( m) LIM/LID
When "0" is set in this parameter, the factory setting is applied in the servo
amplifier.
Each
axis
1000 0
to
65535
PS03
**LID Linear encoder resolution setting Denominator
Set the denominator for parameter No.PS03.
When "0" is set in this parameter, the factory setting is applied in the servo
amplifier.
Each
axis
1000 0
to
65535
Содержание MELSERVO-J3W Series
Страница 17: ...8 MEMO ...
Страница 27: ...1 FUNCTIONS AND CONFIGURATION 1 10 MEMO ...
Страница 87: ...4 STARTUP 4 14 MEMO ...
Страница 117: ...5 PARAMETERS 5 30 MEMO ...
Страница 129: ...6 GENERAL GAIN ADJUSTMENT 6 12 MEMO ...
Страница 185: ...10 CHARACTERISTICS 10 8 MEMO ...
Страница 241: ...11 OPTIONS AND AUXILIARY EQUIPMENT 11 56 MEMO ...
Страница 274: ...13 USING A LINEAR SERVO MOTOR 13 25 1 2 3 4 ...