8 - 23
Chapter 8 HPR Control
8.4 Selection of the HPR setting condition
8.4.1 Outline of the HPR setting condition
If executing the home position return (HPR) when selecting "0: Need to pass servo
motor Z-phase after power on" with the servo parameter of the servo amplifier
"Function selection C-4 (PC17)", it is necessary that the servomotor has been rotated
more than one revolution and passed the Z phase (Motor reference position signal)
and that the zero point pass signal ([Md.108] Servo status (low-order buffer memory
address): b0) has turned ON.
When selecting "1: Not need to pass servo motor Z-phase after power on" with
"Function selection C-4 (PC17)", it is possible to turn the zero point pass signal
([Md.108] Servo status (low-order buffer memory address): b0) ON without passing the
zero point.
Buffer memory address (low-order)
[Md.108] Servo status: b0
2476+100n
n: Axis No.-1
Data setting
To select the "HPR setting condition", set the "servo parameter" shown in the
following table.
Servo parameters are set for each axis.
The "HPR setting condition" is stored into the following buffer memory addresses.
Setting item
Setting
value
Setting details
Buffer memory address
Function selection C-4
(PC17)
0 : Need to pass servo motor Z-phase after
power on
1 : Not need to pass servo motor Z-phase
after power on
28480+100n
n: Axis No.-1
: Refer to Section 5.2.8 "Servo parameters" for information on the storage details.
Precautions during operation
(1) Set "Function selection C-4 (PC17)", and then turn off the power supply of the
servo amplifier once and switch it on again to make that parameter setting
valid.
Содержание MELSEC Q Series
Страница 1: ...MELSEC Q QD77GF Simple Motion Module User s Manual Positioning Control QD77GF4 QD77GF8 QD77GF16 ...
Страница 2: ......
Страница 30: ...A 28 MEMO ...
Страница 32: ...MEMO ...
Страница 97: ...3 29 Chapter 3 Specifications and Functions MEMO ...
Страница 102: ...3 34 Chapter 3 Specifications and Functions MEMO ...
Страница 282: ...5 162 Chapter 5 Data Used for Positioning Control MEMO ...
Страница 374: ...7 16 Chapter 7 Memory Configuration and Data Process MEMO ...
Страница 376: ...MEMO ...
Страница 400: ...8 24 Chapter 8 HPR Control MEMO ...
Страница 425: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Страница 528: ...9 128 Chapter 9 Major Positioning Control MEMO ...
Страница 554: ...10 26 Chapter 10 High Level Positioning Control MEMO ...
Страница 586: ...11 32 Chapter 11 Manual Control MEMO ...
Страница 800: ...16 54 Chapter 16 Troubleshooting MEMO ...
Страница 829: ...Appendix 29 Appendices 3 QD77GF16 Unit mm inch 115 4 53 3 0 12 23 0 91 27 4 1 08 98 3 86 4 0 16 ...
Страница 830: ...Appendix 30 Appendices MEMO ...
Страница 833: ......