16 - 29
Chapter 16 Troubleshooting
Related buffer memory address
Set range
(Setting with sequence program)
Remedy
Refer to Section 5.3
"List of positioning data"
<Maximum radius>
536870912
Correct the positioning data.
(Refer to Section 9.2.10 or 9.2.11)
<LOOP to LEND>
1 to 65535
Set 1 to 65535 in the repeating time of LOOP. (Refer to
Section 9.2.22)
ABS setting direction in the unit
of degree
0: Shortcut
1: Clockwise
2: Counterclockwise
• Set the ABS setting direction in the unit of degree within the
setting range.
• Set "0" when the software stroke limits are valid. (Refer to
Section 9.1.5)
4350+100n
Software stroke limit
upper limit
• [mm] [inch] [PLS]
–2147483648 to 2147483647
• [degree]
0 to 35999999
Invalidate the software stroke limit.
(To invalidate, set the software stroke limit upper limit value to
the software stroke limit lower limit value.)
(Refer to Section 9.1.5)
18+150n
19+150n
Software stroke limit
lower limit
20+150n
21+150n
Operation setting for
incompletion of HPR
<Operation setting for incompletion of
HPR>
0, 1
• Start after the HPR is executed.
• Switch the control mode after the HPR is executed.
• For systems which can operate the positioning control and
speed-torque control though the HPR request is ON, set "1"
to the setting value of the operation setting at HPR
incomplete.
87+150n
— —
Use a servo amplifier which supports the speed-torque
control.
— —
Clear the setting of the CPU module parameter "Output at
error stop".
—
—
The flash ROM is expected to be at the end of its writable life.
5901
<Parameter initialization request>
1: Parameter initialization is requested
Return the parameter to that set at the time of delivery from
the plant. (Refer to Section 14.2)
n: Axis No.-1
Содержание MELSEC Q Series
Страница 1: ...MELSEC Q QD77GF Simple Motion Module User s Manual Positioning Control QD77GF4 QD77GF8 QD77GF16 ...
Страница 2: ......
Страница 30: ...A 28 MEMO ...
Страница 32: ...MEMO ...
Страница 97: ...3 29 Chapter 3 Specifications and Functions MEMO ...
Страница 102: ...3 34 Chapter 3 Specifications and Functions MEMO ...
Страница 282: ...5 162 Chapter 5 Data Used for Positioning Control MEMO ...
Страница 374: ...7 16 Chapter 7 Memory Configuration and Data Process MEMO ...
Страница 376: ...MEMO ...
Страница 400: ...8 24 Chapter 8 HPR Control MEMO ...
Страница 425: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Страница 528: ...9 128 Chapter 9 Major Positioning Control MEMO ...
Страница 554: ...10 26 Chapter 10 High Level Positioning Control MEMO ...
Страница 586: ...11 32 Chapter 11 Manual Control MEMO ...
Страница 800: ...16 54 Chapter 16 Troubleshooting MEMO ...
Страница 829: ...Appendix 29 Appendices 3 QD77GF16 Unit mm inch 115 4 53 3 0 12 23 0 91 27 4 1 08 98 3 86 4 0 16 ...
Страница 830: ...Appendix 30 Appendices MEMO ...
Страница 833: ......