The precautions for wiring the Simple Motion module are given below. Refer to this
section as well as Section 4.1.3 "Handling precautions" when carrying out the work.
4.3.1 Precautions for wiring
DANGER
Completely turn off the externally supplied power used in the system before installation or
wiring. Not doing so could result in electric shock or damage to the product.
CAUTION
Check the layout of the terminals and then properly route the wires to the module.
Connectors for external input wiring must be crimped or pressured with the tool specified by the
manufacturer, or must be correctly soldered. Insufficient connections may cause short circuit,
fire, or malfunction.
Be careful not to let foreign matter such as sawdust or wire chips get inside the module. These
may cause fires, failure or malfunction.
The top surface of the module is covered with protective films to prevent foreign objects such as
cable off cuts from entering the module when wiring. Do not remove this film until the wiring is
complete. Before operating the system, be sure to remove the film to provide adequate
ventilation.
Connect a CC-Link IE Field Network cable to a CC-Link IE Field Network cable connector.
Otherwise, failure may be caused.
When removing the cable from the module, do not pull the cable. Hold the connector that is
connected to the module. Pulling the cable that is still connected to the module may cause
malfunction or damage to the module or cable.
The external input/output signal cable and the communication cable should not be routed near
or bundled with the main circuit cable, power cable and/or other such load - carrying cables
other than those for the PLC. These cables should be separated by at least 100mm (3.94inch)
or more. They can cause electrical interference, surges and inductance that can lead to mis-
operation.
The shielded cable for connecting Simple Motion module can be secured in place. If the
shielded cable is not secured, unevenness or movement of the shielded cable or careless
pulling on it could result in damage to the Simple Motion module, servo amplifier or shielded
cable or defective cable connections could cause mis-operation of the unit.
If the external input/output signal cable and the power line must be adjacently laid (less than
100mm (3.94inch)), use a shielded cable. Ground the shield of the cable securely to the control
panel on the Simple Motion module side. (A wiring example is given on this section "[1]
Precautions for wiring".)
Forcibly removal the cable from the Simple Motion module will damage the Simple Motion
module and cables.
Содержание MELSEC Q Series
Страница 1: ...MELSEC Q QD77GF Simple Motion Module User s Manual Positioning Control QD77GF4 QD77GF8 QD77GF16 ...
Страница 2: ......
Страница 30: ...A 28 MEMO ...
Страница 32: ...MEMO ...
Страница 97: ...3 29 Chapter 3 Specifications and Functions MEMO ...
Страница 102: ...3 34 Chapter 3 Specifications and Functions MEMO ...
Страница 282: ...5 162 Chapter 5 Data Used for Positioning Control MEMO ...
Страница 374: ...7 16 Chapter 7 Memory Configuration and Data Process MEMO ...
Страница 376: ...MEMO ...
Страница 400: ...8 24 Chapter 8 HPR Control MEMO ...
Страница 425: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Страница 528: ...9 128 Chapter 9 Major Positioning Control MEMO ...
Страница 554: ...10 26 Chapter 10 High Level Positioning Control MEMO ...
Страница 586: ...11 32 Chapter 11 Manual Control MEMO ...
Страница 800: ...16 54 Chapter 16 Troubleshooting MEMO ...
Страница 829: ...Appendix 29 Appendices 3 QD77GF16 Unit mm inch 115 4 53 3 0 12 23 0 91 27 4 1 08 98 3 86 4 0 16 ...
Страница 830: ...Appendix 30 Appendices MEMO ...
Страница 833: ......