5 - 45
Chapter 5 Data Used for Positioning Control
[Pr.42] External command function selection
Select a command with which the external command signal should be associated.
0: External positioning start
The external command signal input is used to start a positioning
operation.
1: External speed change request
The external command signal input is used to change the speed
in the current positioning operation. The new speed should be set
in the "[Cd.14] New speed value"
2: Speed-position, position-speed switching request
The external command signal input is used to switch from the
speed control to the position control while in the speed-position
switching control mode, or from the position control to the speed
control while in the position-speed switching control mode.
To enable the speed-position switching control, set the "[Cd.24]
Speed-position switching enable flag" to "1".
To enable the position-speed switching control, set the "[Cd.26]
Position-speed switching enable flag" to "1".
3: Skip request
The external command signal input is used skip the current
positioning operation.
4: High speed input request
The external command signal input is used to execute the mark
detection. And, also set to use the external command signal in the
synchronous control.
POINT
To enable the external command signal, set the "[Cd.8] External command valid" to
"1".
[Pr.83] Speed control 10 x multiplier setting for degree axis
Set the speed control 10 x multiplier setting for degree axis when you use
command speed and speed limit value set by the positioning data and the
parameter at "[Pr.1] Unit setting" setup degree by ten times at the speed.
0: Invalid
1: Valid
Normally, the speed specification range is 0.001 to 2000000.000[degree/min], but
it will be decupled and become 0.01 to 20000000.00[degree/min] by setting
"[Pr.83] Speed control 10 x multiplier setting for degree axis" to valid.
Note) The speed control 10 x multiplier setting for degree axis is included in
detailed parameters 2, but it will be valid at the rising edge (OFF to ON) of
the PLC READY signal [Y0].
1: Refer to Section 13.7.10 "Speed control 10 x multiplier setting for degree axis
function" about speed control 10 x multiplier setting for degree axis.
[Pr.83] setting value
Value set with GX Works2
(unit)
Value set with sequence program (unit)
0 : Invalid
0.001 to 2000000.000 (degree/min)
1 to 2000000000 (
10
-3
degree/min)
1 : Valid
0.01 to 20000000.00 (degree/min)
1 to 2000000000 (
10
-2
degree/min)
Содержание MELSEC Q Series
Страница 1: ...MELSEC Q QD77GF Simple Motion Module User s Manual Positioning Control QD77GF4 QD77GF8 QD77GF16 ...
Страница 2: ......
Страница 30: ...A 28 MEMO ...
Страница 32: ...MEMO ...
Страница 97: ...3 29 Chapter 3 Specifications and Functions MEMO ...
Страница 102: ...3 34 Chapter 3 Specifications and Functions MEMO ...
Страница 282: ...5 162 Chapter 5 Data Used for Positioning Control MEMO ...
Страница 374: ...7 16 Chapter 7 Memory Configuration and Data Process MEMO ...
Страница 376: ...MEMO ...
Страница 400: ...8 24 Chapter 8 HPR Control MEMO ...
Страница 425: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Страница 528: ...9 128 Chapter 9 Major Positioning Control MEMO ...
Страница 554: ...10 26 Chapter 10 High Level Positioning Control MEMO ...
Страница 586: ...11 32 Chapter 11 Manual Control MEMO ...
Страница 800: ...16 54 Chapter 16 Troubleshooting MEMO ...
Страница 829: ...Appendix 29 Appendices 3 QD77GF16 Unit mm inch 115 4 53 3 0 12 23 0 91 27 4 1 08 98 3 86 4 0 16 ...
Страница 830: ...Appendix 30 Appendices MEMO ...
Страница 833: ......