14
Parameter change-over
14.2
Configuring the definable parameter list by means of parameterisation
796
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.2
Configuring the definable parameter list by means of parameterisation
The following application example shows the necessary procedure for configuring the list without
using the »Engineer« parameterisation dialog.
Task:
The
LS_WriteParamList
SB is to be used to write to parameters
,
and
Compiling the parameter list
In
, specify the above-named parameters in the <Code>,<Subcode> format:
•
= 12.000
•
= 26.001
•
= 27.001
•
Entering values for the parameters (value set 1)
In
, specify the values to be used to describe the selected parameters. The values are
entered according to the scaling format/scaling factor of the respective parameter.
•
= <value> for list entry 1 (in our example: for parameter
•
= <value> for list entry 2 (in our example: for parameter
)
•
= <value> for list entry 3 (in our example: for parameter
)
These values are used in the writing process if the two
bSelectWriteValue_1
and
bSelectWriteValue_2
inputs are not assigned or both set to FALSE.
Entering other values for the parameters (value sets 2 ... 4)
If required, up to three other sets can be set in the same way in
to
which can optionally be written to the parameters. The decision as to which value set is finally used
is dependent upon the assignment of the two bSelectWriteValue_1 and bSelectWriteValue_2
inputs:
Note!
Gaps in the parameter list (setting = 0.000) are permissible and are skipped in the
process.
Invalid parameter entries are not accepted when being entered.