Function library
17.1
Function blocks | L_GainOffset_1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
17.1.86
L_GainOffset_1
This FB can amplify an analog input signal and add an offset to it afterwards. Preferably to be
interconnected directly after the analog input terminals.
• The internal calculations (addition and subtraction) are carried out with 32 bits without
overflow/underflow. Division is not remainder considered.
• Gain and offset are selected via FB inputs.
• The value provided at the
nOut_a
output is internally limited to ±199.99 %.
Inputs
Outputs
Function
Designator
Data type
Information/possible settings
nIn_a
INT
Input signal
• Scaling: 16384
≡
100 %
nGain_a
INT
Gain factor
• Scaling: 16384
≡
100 %
• 199.99 %
≈
2
nOffset_a
INT
Offset
• Scaling: 16384
≡
100 %
Designator
Data type
Value/meaning
nOut_a
INT
Output signal
• Internal limitation to ±199.99 %