Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
669
9
Diagnostics & error management
9.9
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PS01: No memory module [xx.0144.00001]
PS02: Par. set invalid [xx.0144.00002]
PS03: Par. set device invalid [xx.0144.00003]
Response
(Lenze setting printed in bold)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Memory module is either not available or not snapped
into place correctly.
• If a memory module has been provided: Plug the
memory module into the slot of the standard device
intended for this purpose.
• If a memory module has been provided: Check if the
memory module has been plugged-in correctly.
Response
(Lenze setting printed in bold)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
The parameter set stored in the memory module is
invalid. The reason for this can be as follows:
• Incomplete storage of the parameter set due to
voltage failure.
• The plugged-in module stems from a device with new
firmware (compare
) or from a different
device type (e.g. 8400 BaseLine).
The error can only be removed by loading the Lenze
setting with the
= "1: On / start" device
command.
• In order to prevent the error, do not switch off the
voltage during the saving process.
• If the parameter set is to be transferred from one
device with a higher version to a device with a lower
version, use the "copy parameter set" function of the
keypad. Make sure that you do not use functions that
are not available in the older device.
Response
(Lenze setting printed in bold)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
The parameter set saved to the memory module is
incompatible to the standard device.
• An incompatibility of the parameter set is caused e.g.
when the memory module of an 8400 HighLine is
plugged into an 8400 StateLine or the parameter set
in the memory module has a higher version than
expected by the standard device.
If the parameter set stored in the memory module is
compatible with the standard device but has a different
(lower) version, this message is only output as
"Information". The message can be eliminated by saving
the parameter set again.
Note:
If you save the parameter set to a higher device version,
you can no longer load this parameter set to a lower
device version.
When the memory modules are replaced, observe the
compatibility:
• OK: StateLine V2.0 to StateLine V3.0
• OK: StateLine V2.0 to HighLine V2.0
• Not OK: HighLine Vx.x to StateLine Vx.x
• Not OK: StateLine V3.0 to StateLine < V3.0