Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
161
5
Motor control (MCTRL)
5.4
V/f characteristic control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4.2.1
Defining the V/f characteristic shape
In principle, four different characteristic shapes can be stipulated:
1.
Linear V/f characteristic
:
For drives for a constant, speed-independent load torque.
2.
Quadratic V/f characteristic
:
For drives with a load torque curve which is quadratic or in relation to speed. Quadratic V/f
characteristics are preferred in the case of centrifugal pumps and fan drives.
3.
User-definable V/f characteristic
(from version 04.00.00 onwards)
:
For drives that require adaptation of the magnetising current by means of the output speed. The
freely definable V/f characteristic can be used e.g. for operation in conjunction with special
machines such as reluctance motors in order to suppress oscillations at the machine or to
optimise energy consumption.
[5-3]
Principle of a linear V/f characteristic (on the left) and a quadratic V/f characteristic (on the right)
4.
Linear V/f characteristic with voltage reduction
(from version 10.00.00 onwards)
:
For drives which often work in partial load operation, the energy-saving V/f characteristic
control (VFCplusEco) offers the opportunity to reduce the voltage at low load in order to save
energy. At higher loads, the voltage reduction is cancelled and a linear characteristic is caused.
The V/f characteristic shape is defined by selecting the corresponding motor control mode in
Tip!
• You can find detailed information on freely definable V/f characteristics in the
subchapter entitled "
Defining a user-defined V/f characteristic
• You can find detailed information on the linear V/f characteristic with voltage reduction
in the chapter entitled "
V/f characteristic control - energy-saving (VFCplusEco)
0
1
0
100
%
N
n
n
U
min
U
out
0
1
0
100
%
N
n
n
U
min
U
out
V/f characteristic shape
Motor control to be selected (C00006)
Linear V/f characteristic
6: VFCplus: V/f linear
Square-law V/f characteristic
8: VFCplus: V/f quadr
User-definable V/f characteristic
10: VFCplus: V/f definable
Linear V/f characteristic with voltage reduction
11: VFCplusEco: V/f energy-saving