Parameter | Name:
C00435 | OxU/I: Offset
Data type: INTEGER_16
Index: 24140
d
= 5E4C
h
Offset of the analog outputs
Setting range
(min. value | unit | max. value)
-199.99
%
199.99
Subcodes
Lenze setting
Info
C00435/1
0.00 %
O1U: Offset
C00435/2
0.00 %
O2U: Offset
C00435/3
0.00 %
O1I: Offset
C00435/4
0.00 %
O2I: Offset
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00436 | OxU: Voltage
Data type: INTEGER_16
Index: 24139
d
= 5E4B
h
Display of the voltage at the analog outputs
Display range
(min. value | unit | max. value)
0.00
V
10.00
Subcodes
Info
C00436/1
O1U: Voltage
C00436/2
O2U: Voltage
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00437 | OxI: Current
Data type: INTEGER_32
Index: 24138
d
= 5E4A
h
Display of the current at the analog outputs
Display range
(min. value | unit | max. value)
0.000
mA
20.000
Subcodes
Info
C00437/1
O1I: Current
C00437/2
O2I: Current
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000