Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
227
5
Motor control (MCTRL)
5.8
Sensorless control for synchronous motors (SLPSM)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Optimising the pole position identification
How to optimise the pole position identification without motion:
1. For optimisation, enable the controller for various rotor displacement angles.
2. After every controller enable, check the optimisation degree displayed in
.
The pole position identification is set optimally if an optimisation degree in the range 70 ...
after every controller enable.
3. When the optimisation degree is > 130 %:
Reduce the setting in
step by step an execute controller enable for various rotor
displacement angles until an optimisation degree < 130 % is displayed.
4. When the optimisation degree is < 70 %:
Increase setting in
step by step and execute controller enable for various rotor
displacement angles until an optimisation degree > 70 % is displayed.
serves to increase or reduce the identified electrical rotor displacement
angle. This can prevent e.g. a reversing of the motor due to the accuracy of identification if
applications require it.
Stop!
In case of a too high setting in
, an impermissible motor current may occur during
pole position identification. In this case, the "Fault" error response occurs and the "Id5:
Pole position identification error" error message entered in the logbook.
In case of aconsiderably too high setting in
:
• The following current monitoring functions can be triggered:
• oC7: Motor overcurrent
• oC11: Clamp operation active
• oC1: Power section - short circuit
• The optimisation degree "0 %" is displayed in
• The time "0 ms" is displayed in