15
Parameter reference
15.2
Parameter list
1148
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02865
Bit 11 Latching of open circuit FreqIn12 or
67
Bit 12 SLVC: No smoothing of
nMotorTorqueAct_a
Bit 13 SLVC: Setpoint feedforward control is
active
Bit 14
Reserved
Bit 15
Reserved
Subcodes
Lenze setting
Info
C02864/1
0x0000
: Optimisations
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Parameter | Name:
C02864 | MCTRL: Optimisiations
Data type: UNSIGNED_16
Index: 21711
d
= 54CF
h
Parameter | Name:
C02865 | MCTRL: Special settings
Data type: UNSIGNED_16
Index: 21710
d
= 54CE
h
From version 12.00.00
Activation of special functions of the internal motor control
Setting range
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Info
Bit 0 No TorqueLimit if TorquemodeOn
From version 12.00.00 onwards
: If sensorless vector
control (
) or servo control (
) are used, in the
"torque control with speed limitation" mode the torque
limitation via
nTorqueMotLimit_a
and
nTorqueGenLimit_a
is also active to limit the torque
setpoint.
If you want to deactivate the torque limitation to retain
the former function, set bit 0 to "1".
0
≡
Torque limitation is active
1
≡
Torque limitation is not active
Bit 1 250ms IMP before DCB
Bit 2 1000ms IMP before DCB
Bit 3 DCB: Current controller and C036
app. to C088
Bit 4 Motorident.: No calculation C73 C75
C76 C77 C78
From version 12.00.00 onwards
: Following successful
motor parameter identification, the current controller
and field controller parameters are calculated as well.
If these parameters are not to be calculated, bit 4 must
be set to "1".
0
≡
Calculate parameter
1
≡
Do not calculate parameter
Automatic motor data identification
Bit 5 Motorident.: Calculation C70 C71
C72
From version 12.00.00 onwards
: Following successful
motor parameter identification, the speed controller
parameters can automatically be calculated as well.
If these parameters are to be calculated, bit 5 must be set
to "1".
0
≡
Do not calculate parameter
1
≡
Calculate parameter