15
Parameter reference
15.2
Parameter list
918
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00561
C00563
Selection list
0 Off
1 On
2 No fan
Subcodes
Info
C00560/1
Switching status - internal fan
C00560/2
Switching status - heatsink fan
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00560 | Fan switching status
Data type: UNSIGNED_8
Index: 24015
d
= 5DCF
h
Parameter | Name:
C00561 | Failure indication
Data type: UNSIGNED_8
Index: 24014
d
= 5DCE
h
Failure display of device fans and motor phases
Selection list
0 No error
1 Error
Subcodes
Info
C00561/1
Internal fan
C00561/2
Heatsink fan
C00561/3
Motor phase U
•
From version 11.00.00
C00561/4
Motor phase V
•
From version 11.00.00
C00561/5
Motor phase W
•
From version 11.00.00
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00563 | Current monitoring: Delay time
Data type: UNSIGNED_32
Index: 24012
d
= 5DCC
h
From version 16.00.00
Setting range
(min. value | unit | max. value)
0.000
s
999.900
Subcodes
Lenze setting
Info
C00563/1
3.000 s
Current monitoring: Delay time overload
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000