Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
1520
17
Function library
17.1
Function blocks | L_Transient_1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
17.1.165.1 Function 0: Evaluate rising signal edges
[17-76] Switching performance for function selection "0: High edge"
Functional sequence
1. A FALSE-TRUE edge at the
bIn
input sets the
bOut
output to TRUE.
2. After the parameterised pulse duration has elapsed, the
bOut
output is reset to FALSE unless
another FALSE/TRUE edge has been set at the
bIn
input.
• If an additional FALSE-TRUE edge occurs at the
bIn
input, the pulse duration starts again from
the beginning, i.e. the
bOut
output can be retriggered.
17.1.165.2 Function 1: Evaluate falling signal edges
[17-77] Switching performance for function selection "1: Low edge"
Functional sequence
1. A TRUE-FALSE edge at the
bIn
inputs sets the
bOut
output to TRUE.
2. After the parameterised pulse duration has elapsed, the
bOut
output is reset to FALSE unless
another TRUE/FALSE edge has been set at the
bIn
input.
• If an additional TRUE-FALSE edge occurs at the
bIn
input, the pulse duration starts again from
the beginning, i.e. the
bOut
output can be retriggered.
Pulse duration
TRUE
FALSE
bOut
t
TRUE
FALSE
bIn
t
Pulse duration
TRUE
FALSE
bOut
t
TRUE
FALSE
bIn
t