Chapter 6. OPERATION
6-4 External Switch Operation
■
External switch input
A total of 16 external switch inputs are available. Each input is called SW1, SW2, etc.
up to SW16. (SW: external switch input)
●
Types of external switch inputs
SW1 to 4 and SW9 to 16 are tied.
SW5 to 8 functions are selected using setup data
C71
to
C74
.
SW9 to 16 are for program selections. Selections are made by entering BCD code or
binary codes in setup data
C75
. When two weights are given for an item, the right
weight is for binary figures and the left is for BCD.
NOTE
• When G.SOAK is cleared using an OR condition and an external switch is on, or PV
enters the G.SOAK width, a G.SOAK wait is cleared.
• When G.SOAK is cleared using an AND condition and an external switch is on and
PV enters the G.SOAK width, a G.SOAK wait is cleared.
• A normal or reverse operation is performed according to setup data setting
C23
when the external switch is off. When the external switch is on, a normal or reverse
operation that is the reverse of setup data setting
C23
is performed.
External
switch number
Function
Detection way
SW1
RUN
Leading edge
SW2
HOLD
Leading edge
SW3
RESET
Leading edge
SW4
ADV
Leading edge
SW5
Selects one of the following functions using setup settings.
SW6
RAMP-E
Leading edge
SW7
FAST
Leading edge
SW8
Clears G.SOAK using the OR condition.
Status
Clears G.SOAK using the AND condition.
Status
MANUAL/AUTO
Leading/trailing edge
AT start/stop
Leading/trailing edge
PV1/PV2 (OFF: PV1, ON: PV2)
Status
AUTO Loading (the DCP551E***** model only)
Leading edge
PV1
→
PV2 standby (See page 5-35.)
Status
PV2
→
PV1 standby (See page 5-35.)
Status
Normal/Reverse operation
Status
SW9
Selects program number, weight 1
Status
SW10
Selects program number, weight 2
Status
SW11
Selects program number, weight 4
Status
SW12
Selects program number, weight 8
Status
SW13
Selects program number, weight 10 or 16
Status
SW14
Selects program number, weight 20 or 32
Status
SW15
Selects program number, weight 40 or 64
Status
SW16
Selects program number, weight 80 or 0
Status
6-8
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...