Chapter 5. FUNCTIONS
■
G.SOAK (Guarantee soak)
G.SOAK on/off state, type and G.SOAK width is set by the segment. G.SOAK are of
three types: segment start point, segment end point and the entire segment.
G.SOAK time is set using the variable parameter
PA46
setting. Any offset between SP
and PV triggers a G.SOAK wait which narrows the distance between SP and PV to guar-
antee the segment execution time. G.SOAK operates not only on SOAK but also on
RAMP segments.
Note, however, that in FAST mode a G.SOAK setting does not trigger a G.SOAK wait.
G.SOAK can be cleared with an external switch input. The following types of clearing
conditions can be selected using setup data setting
C71
to
C74
.
(1) G.SOAK is cleared when an external switch contact is set to on or when PV meets
the G.SOAK clearing conditions.
(2) G.SOAK is cleared when an external switch contact is set to on and PV meets the
G.SOAK clearing conditions.
• G.SOAK at start of segment
PV and SP are compared at the beginning of the segment. The segment starts when
the absolute value of the difference continues beyond the G.SOAK time and becomes
narrower than G.SOAK width.
A G.SOAK wait state continues until these conditions are met which is announced by
the flashing of the linear LED on the left of the profile display.
The operating condition is the same as HOLD at the beginning of a segment (time =
0).
5-17
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...