Chapter 7. PARAMETER SETUP
●
C99
(PV1 zener barrier adjustment)
●
C100
(PV2 zener barrier adjustment)
The adjustment described below must be performed when a zener barrier is used.
(1) Turn off the DCP551. When installation and wiring is completed, short-circuit
A
and
B
on the resistance temperature detector.
(2) Turn on the DCP551 and set setup data
C98
to 241.
(3) Display setup data
C99
and
C100
.
(4) Press the
ENTER key
to display the difference in resistance (A-B) between zener
barriers connected to wire
A
and wire
B
.
(5) Press the
ENTER key
to store the difference in resistance values (A-B) in the
DCP551.
(6) Press the
DISP key
to return to the normal display mode.
(7) urn off the DCP551 and disconnect the wire between
A
and
B
.
HANDLING PRECAUTIONS
• Adjust the resistance in the zener barriers connected to wire A and B to 20
Ω
or less. Adjustment is not possible if the resistance is higher than 20
Ω
.
• This adjustment is not required for inputs other than resistance temperature
detectors or when zener barriers are not to be used.
• When a zener barrier has been adjusted, compensation is performed for this
zener barrier. When resistance temperature detector inputs not employing
zener barriers are to be used, perform the above adjustment without the
zener barriers.
!"
# !"
$
$
$
$
$
$
7-33
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...