Chapter 4. WIRING
4-3 Making Terminal Connections
To connect a line to the terminals, use crimp-style solderless wire connectors that fit an M3.5 screw.
HANDLING PRECAUTIONS
• If the DCP551 is mounted in a location subject to noticeable vibration or
impact, be sure to use round crimp-style solderless wire connectors to prevent
lines from becoming disconnected from the terminals.
• Be careful not to allow any of the crimp-style solderless wire connectors to
touch adjacent terminals or connectors.
• The terminal screws shall be tightened to 0.78 to 0.98 N
•
m torque.