Chapter 11. SPECIFICATIONS
Item
Specifications
Input section
External switch
input section
Display and
setting section
Cold junction compensation system
Internal or external compensation (at 0 C) selectable
Scaling
-19999 to +20000U (Only linear input can sets. Reverse scaling and optional decimal point position can set.)
Root extraction
Drop out 0.2 to 10.0%. It is possible to set DC current and DC voltage range.
PV equalizer
(linearization)
PV1: 9 broken line (setting to 10 point)
PV2: 19 broken line (setting to 20 point)
Input bias
-1000 to +1000U variable
Digital filter
0.0 to 120.0sec variable (0.0: Filter off)
Number of input point
16 points
Open terminal voltage
8.5V
0.5V during common terminal ((12) and (40) terminals) and every input
terminal (under operating conditions)
Terminal current in case of short circuit
Current to run every terminal is about 6mA (under operating conditions)
Allowable contact resistance
(no-voltage contact)
On condition: Lower than 250 (under operating conditions)
Off condition: Higher than 100 k (under operating conditions)
Allowable residual current
(open collector ON)
Lower than 2V (under operating conditions)
Leakage current
(open collector OFF)
Lower than 0.1mA (under operating conditions)
Allocation (fixed)
RUN, HOLD, RESET, ADV, program number
Allocation (variable)
RAMP-E, FAST, AT, AUTO/MANUAL, G.SOAK reset, forward-reverse operation,
auto load* , PV1/2 selection
Display panel 1
Digital 5 digits, 7 segments, green color
Indicates PV and other data on basic display status, indicates an item code on parameter setting status.
Display panel 2
Digital 5 digits, 7 segments, orange color
Indicates SP, output %, and other data on basic display status, indicates a set point of item on parameter setting status.
On detection Min. hold time
0.2s (program number is 0.4s)
Input sampling cycle
0.1s
Segment number display
Digital 2 digits, 7 segments, green color
Indicates a segment number on basic display status, indicates a item number on parameter setting status.
Indicates an alarm code number when an alarm occurs.
Program number display
Digital 2 digits, 7 segments, green color
Indicates a program number on basic display status.
Message display panel
Indicates output graph, deviation graph, event status, program tag, and other data on basic display status,
Indicates a reference message on parameter setting and program setting.
Indicates a operation contents and operation result on memory card operation.
Profile display
7 flat LED, orange color
Indicates the rising, soaking, and falling tendencies of program pattern.
Each status display
22 flat LED
Mode : RUN, HLD, MAN, PRG (green color)
Display contents: PV, SP, OUT, TM, CYC, SYN, DEV (green color)
Battery voltage : BAT (red color) (flickers when the battery voltage has dropped.)
Status : AT (green color)
Event : EG1, EG2 (red color)
Operating keys
18 rubber keys (DCP551E***** model), 16 ruber keys (DCP551F***** model)
Loader connection port
1 (Using exclusive connection cable, stereo pin jack)
Connectable output type
No-voltage contact (relay contact), and open corrector (sink current toward 0V)
* : available on the DCP551E***** model only
11-2
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...