Chapter 7. PARAMETER SETUP
0
C 72
72
External switch input RSW6
0
C 73
73
External switch input RSW7
0
C 74
74
External switch input RSW8
0: BCD4 bit x 2 digits
1: binary 7 bits
0
C 75
75
External switch input RSW9
to 16 (program selection)
0 to 127
[Description:]
----- is displayedandsetting cannot be performedon
model without communications.
When
C76
is set to 0, the communication function is not
activated.
0
C 76
76
Communication address
0: 9600bps
1: 4800bps
2: 2400bps
3: 1200bps
[Description:]
----- is displayedandsetting cannot be performedon
model without communications.
0
C 77
77
Transmission rate
0: 8 bits, even parity, 1 stop bit
1: 8 bits, no parity, 2 stop bits
[Description:]
----- is displayedandsetting cannot be performedon model without
communications.
0
C 78
78
Transmission code
0: CPL
1: ST221 (no PV trend)
2: ST221 (PV trend)
[Description:]
----- is displayedandsetting cannot be performedon model without
communications.
0
C 79
79
Communication
0 : RS-485
1 : RS-232C
[Description:]
----- is displayedandsetting cannot be performedon model without
communications.
0
C 80
80
Communication method
[Description:]
Can only be referencedfor mechanical service use.
Ð
C 81
81
ROM ID
Ð
C 82
82
ROM ITEM
Ð
C 83
83
ROM revision
Ð
C 85
85
CPU boardID
Ð
C 86
86
I/O boardID
[Description:]
----- is displayedandsetting cannot be performed.
----
C 87
87
Unused
----
C 88
88
Unused
----
C 89
89
Unused
1
C 90
90
PID type
0: Yes
1: No
0
C 91
91
PV1 burnout
0: Yes
1: No
[Description:]
----- is displayedandsetting cannot be performedon
model with one PV input channel.
0
C 92
92
PV2 burn out
0: Does not go on a secondtime off in time proportional cycle.
1: Goes on a secondtime in time proportional cycle.
0
C 93
93
Time proportional output system
[Description:]
----- is displayedandsetting cannot be performed.
----
C 94
94
Unused
Ð
C 84
84
Data version
0 : NOP (does not function)
1 : RAMP-E
2 : FAST
3 : G.SOAK is clearedusing OR
4 : G.SOAK is clearedusing AND
5 : MANUAL/AUTO
6 : AT start/terminate
7 : PV1/PV2
8 : Auto load
9 : PV1
®
PV2 wait
10: PV2
®
PV1 wait
11: NOP (does not function)
12: Normal operation/reverse operation
0
C 71
71
External switch input RSW5
0: Improved
1: Compatible with Mark 1
7-26
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...