Chapter 5. FUNCTIONS
5-6 Output Processing Functions
■
Control output
When the controller function is used, the control output is processed as shown below.
●
Current output (with setup data
C21
set to 1)
P / l / d / rE
C23
PA17
PA43
PA14
oL / oH
PA16
oL / oH
!
PA08
PA09
PA10
! "
# $
C33
C34
# %& ' $
C32
%& '
# ( #
# (
$ # (
# )#*+
,
- ./
$
C35
C36
5-37
HANDLING PRECAUTIONS
The MANUAL mode cannot be invoked
during ON-OFF control. (MANUAL
mode can be accessed in READY
mode which disables ON-OFF control.
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...