Chapter 8. PROGRAM SETUP
■
Setting PID groups and output limiter group number items
(1) In the set value display state, move to the PID group, output limiter group number
item to be set for the segment on the programming map.
(2) Press the
ENTER key
to make display panel 1 flash (registration of first setting).
(3) Use the
↑
,
↓
,
←
, and
→
keys
to make the first setting (PID group number).
Setting range: ON-OFF, PID 0 to 9, PID A
(4) Press the
ENTER key
to stop the flashing on display panel 1 and display panel 2
starts flashing. (Start of second setting)
(Pressing the
FUNC
and
CLR keys
causes display panel 1 and 2 to return to unset
state “
Pld 0/otL 0
” and the flashing stops.)
(5) Use the
↑
,
↓
,
←
, and
→
keys
to make the second setting (output limiter group num-
ber).
Setting range: 0 to 9
(6) Press the
ENTER key
to stop the flashing on display panel 2.
(Pressing the
FUNC
and
CLR keys
causes display panel 2 to return to unset state
“
Pld 0/otL 0
” and the flashing stops.)
●
Display
• Unset values are indicated as “
Pld 0/otL 0
”.
• When setup data
C21
is set to 0 and the programmer function is selected or when
C58
is set to 1, PID groups, output limiter group number items are skipped and not dis-
played.
NOTE
When a PID group or output limiter group number is not 0 or both are something other
than 0, they use a subfunction. A subfunction cannot be used when a setting has not
been made “
Pld 0/otL 0
”.
HANDLING PRECAUTIONS
• When a set value for a PID group number is 0, it is a sequel to a PID number
in a previous segment. When the set value for a PID group number in the first
segment is 0, the set value is 1.
• When a set value for an output limiter group number is 0, it is a sequel to an
output limiter group number in a previous segment. When the set value for
an output limiter group number in the first segment is 0, the set value is 1.
C O N T R O L
M V O U T L I M I T E R
8-12
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...