DCP551 Parameter Work Sheet
No.
Item code
Item
Factory default
-
User
Settings and descriptions
settings
settings
73
P-A4
Proportional band (PID group A4) 100.0
0.0 to 1000.0%
(0.0: On-off control)
74
I-A4
Integral time (PID group A4)
0
0 to 3600sec
(0: no integral operation)
75
d-A4
Derivative time (PID group A4)
0
0 to 1200sec
(0: no derivative operation)
76
rE-A4
Manual reset (PID group A4)
50.0
0.0 to 100.0%
77
CP-A4
Switching point (PID group A4) 4000 SPU
–19999 to +20000 SPU
78
tP-A4
Tuning point (PID group A4)
3500 SPU
–19999 to +20000 SPU
79
P-A5
Proportional band (PID group A5) 100.0
0.0 to 1000.0%
(0.0: On-off control)
80
I-A5
Integral time (PID group A5)
0
0 to 3600sec
(0: no integral operation)
81
d-A5
Derivative time (PID group A5)
0
0 to 1200sec
(0: no derivative operation)
82
rE-A5
Manual reset (PID group A5)
50.0
0.0 to 100.0%
83
CP-A5
Switching point (PID group A5) 5000 SPU
–19999 to +20000 SPU
84
tP-A5
Tuning point (PID group A5)
4500 SPU
–19999 to +20000 SPU
85
P-A6
Proportional band (PID group A6) 100.0
0.0 to 1000.0%
(0.0: On-off control)
86
I-A6
Integral time (PID group A6)
0
0 to 3600sec
(0: no integral operation)
87
d-A6
Derivative time (PID group A6)
0
0 to 1200sec
(0: no derivative operation)
88
rE-A6
Manual reset (PID group A6)
50.0
0.0 to 100.0%
89
CP-A6
Switching point (PID group A6) 6000 SPU
–19999 to +20000 SPU
90
tP-A6
Tuning point (PID group A6)
5500 SPU
–19999 to +20000 SPU
91
P-A7
Proportional band (PID group A7) 100.0
0.0 to 1000.0%
(0.0: On-off control)
92
I-A7
Integral time (PID group A7)
0
0 to 3600sec
(0: no integral operation)
93
d-A7
Derivative time (PID group A7)
0
0 to 1200sec
(0: no derivative operation)
94
rE-A7
Manual reset (PID group A7)
50.0
0.0 to 100.0%
95
CP-A7
Switching point (PID group A7) 20000SPU
20000 SPU (tied)
(fixed)
96
tP-A7
Tuning point (PID group A7)
6500 SPU
–19999 to +20000 SPU
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...