Chapter 8. PROGRAM SETUP
■
Setting PV start items
(1) In the set value display state, move to the PV start item to be set for the segment on
the programming map.
(A PV start item is a program setting and is the same for each segment.)
(2) Press the
ENTER key
to make display panel 2 flash (registration of first setting).
(3) Use the
↑
,
↓
,
←
, and
→
keys
to make the first setting – setting the PV start value.
Setting range:0 to 3
0: no PV start
1: descending PV start
2: ascending PV start
3: bi-directional PV start
(4) Press the
ENTER key
to stop the flashing on display panel 2.
(Pressing the
FUNC
and
CLR keys
causes display panel 2 to return to unset state
“
0
” and the flashing stops.)
●
Display
• A PV start item is a program setting and is the same for each segment.
• When setup data
C60
is set to 1, a PV start item on the programming map is skipped
and not displayed.
NOTE
A PV start item setting does not use subfunctions.
P V S T A R T
8-16
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...