Chapter 7. PARAMETER SETUP
■
Detailed descriptions of setup data settings
●
C07
(PV1 cold junction compensation)
●
C17
(PV2 cold junction compensation)
• This is a selection for cold junction compensation for thermocouples.
• When set to 1, perform 0°C compensation using a cold junction compensation device
outside the DCP551
●
C08
(PV1 square root extraction)
●
C09
(PV1 square root extraction dropout)
●
C18
(PV2 square root extraction)
●
C19
(PV2 square root extraction dropout)
• Flow pressure detected by the orifice of a normal differential pressure type flowmeter
is proportional to the power 2 of the flow rate signal. Consequently, square root
extraction is used when a uniform signal is needed.
When the input in the square root extraction is
C09
or less than the dropout set in
C19
, an output of 0% can be obtained in the square root process.
• Square root extraction is not performed when
C08
and
C18
are set to 0.
●
C46
(auxiliary output 1 lower limit)
●
C47
(auxiliary output 1 upper limit)
●
C49
(auxiliary output 2 lower limit)
●
C50
(auxiliary output 2 upper limit)
• This is the scaling setting of the auxiliary output. The high and low values for the
upper and lower limits can be reversed.
• The example below shows that the output from auxiliary output 1 is 12mA when MV
is 100% and 20mA when MV is 0%. As shown, a 200% MV value is required to gen-
erate an output of 4mA.
Thus
C46
is set to 200.0 and
C47
is set to 0.0.
´
7-28
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...