Chapter 8. PROGRAM SETUP
●
When the event is a time event
(1) In the set value display state, move to the event item to be set for the segment on the
programming map.
(2) Press the
ENTER key
to make display panel 1 flash (registration of first setting).
(3) Use the
↑
,
↓
,
←
, and
→
keys
to make the first setting (On Time setting).
Setting range: 0:00 to 500:00, 0.0 to 3000.0
(Time units are selected using setup data
C62
to set Hour/min, Min/sec, 0.1 sec.
Since a colon “:” cannot be displayed, the decimal point is used instead.
(4) Press the
ENTER key
to stop the flashing on display panel 1 and display panel 2
starts flashing. (Start of second setting)
(Pressing the
FUNC
and
CLR keys
causes display panel 1 and 2 to return to unset
state “-----” and the flashing stops.)
(5) Use the
↑
,
↓
,
←
, and
→
keys
to make the second setting (Off Time setting).
Setting range: On time s0:01 to 500:00, Off time s0.1 to 3000.0
(6) Press the
ENTER key
to stop the flashing on display panel 2.
(Pressing the
FUNC
and
CLR keys
causes display panel 2 to return to unset state
“-----” and the flashing stops.)
●
Display (time event)
• Unset values are indicated as “-----”.
• When the On Time is set to 500:00 or 3000.0, an Off Time cannot be set.
NOTE
A time event setting consists of one setting, an On Time, or two settings, an On Time
and an Off Time. When both settings are made a subfunction can be used. In unset state
“-----” a subfunction cannot be used.
HANDLING PRECAUTIONS
In a time event, an On Time or Off Time setting that is the same as or exceeds
the segment time is invalid.
Note, however, that when there is a G.SOAK wait at the end of a segment or an
END mode at the end of a program, an On Time or Off Time setting that is the
same as the segment time is valid.
8-8
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...