14
DCP551 Parameter Work Sheet
No.
Item code
Item
Factory default
-
User
Settings and descriptions
settings
settings
1
ConSt
Control mode
0
0 : Program run mode
1 : Constant value control mode
2
SP
Set point
0
Within setup
C66
to
C67
setting (SP limit)
3
P
Proportional band
100.0
0.0 to 1000.0%
(0.0 : On-off control)
4
I
Integral time
0
0 to 3600sec
(0: no integral operation)
5
d
Derivative time
0
0 to 1200sec
(0: no derivative operation)
6
rE
Manual reset
50.0
0.0 to 100.0%
7
oL
Manipulated variable lower limit
0.0
–5.0 to upper limit %
8
oH
Manipulated variable upper limit
100.0
Lower limit to +105.0%
■
Constant value control data setting