Chapter 7. PARAMETER SETUP
●
PA17
(PID computation initialize manipulated variable)
Under the conditions listed below, a PID computation starts using the value set in
PA17
.
• When there is a mode change from READY AUTO to RUN AUTO.
• When the controller is powered up in RUN (or HOLD, FAST, END) AUTO mode.
• When auto-tuning ends.
Since the PV, SP and PID parameters affect a PID computation, the first manipulated
variable of a PID computation may not be the same as the value set in
PA17
.
●
PA31
to
PA38
(event on delay groups 1 to 4, event/delay time)
• On delay can be performed on up to 4 events.
•
PA31
,
PA33
,
PA35
and
PA37
determine which events are to be processed.
• In a code event involving several event outputs, event on delay has to be set separate-
ly for each output.
• All processes including event output standby on/off are processed before on delay
processing. When the event output ON condition remains on for longer than the on
delay time, the event output stays on.
• This is shown in the diagram below.
●
PA41
(EG1 LED display event number)
The console
EG1
LED lights when an event number set in
PA41
goes on and is off
when it goes off. Note, however, that the
EG1
LED is off when
PA41
is set to 0.
●
PA42
(EG2 LED display event number)
The console
EG2
LED lights when an event number set in
PA42
goes on and is off
when it goes off. Note, however, that the
EG2
LED is off when
PA42
is set to 0.
●
PA43
(PID computation initialize)
When SP changes abruptly due to ADV, the derivative action of a PID computation,
may cause an excessive change in the manipulated variable of the computation.
For this reason, the initialization of a PID computation is performed to suppress an
excessive change.
But the initialization of a PID computation means that PID computation continuity is
lost which may affect operating conditions. A
PA43
setting allows the user to turn on or
off initialization and determine its conditions.
Time
Event output turns on
Event output turns off
Event output turns off
On delay time
The requirement event turns on
The requirement event turns off
The requirement
event turns off
7-11
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...