Chapter 5. FUNCTIONS
●
Code event
Several events are used as one group and the number of output points are output as one
parallel code number. Assigning code numbers to event outputs has the same effect as
increasing the number of physical output points.
•
Code event
Set event type to code event and set the number of output points (1 to 8) in auxiliary
setting 1. An output code value (0 to 255) can be set for each segment. A binary
coded low-order bit for the set number of output points is output.
The previous setting is valid until the program reaches a segment with a new setting.
Note, however, that unless a setting is made in the first segment, the program will
assume that a set value of 0 is set in the first segment.
Segment
Set value
Code value
1 in event 3
Code value
2 in event 4
Code value
4 in event 5
Output code
1
2
5
4
3
Not set
3
Not set
6
0
OFF
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
0
OFF,OFF,OFF
0, 0,
0
3
OFF,ON,ON
0, 1, 1
3
OFF,ON,ON
0, 1, 1
6
ON,ON,OFF
1, 1, 0
0
OFF,OFF,OFF
0 , 0,
0
Example: Settinga code event involving3 output points in event 3
The table below shows the output state when a value of 3 is set in segment 2, a value of 6 is
set in segment 4 and a value of 0 is set in segment 5.
5-12
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...