DCP551 Parameter Work Sheet
No.
Item code
Item
Factory default
-
User
Settings and descriptions
settings
settings
66
C 66
SP limit lower limit
PV1 range
–19999 to +20000 SPU
lower limit
67
C 67
SP limit upper limit
PV1 range
–19999 to +20000 SPU
upper limit
71
C 71
External switch input RSW5
0
0 : NOP (does not function.)
1 : RAMP—E
2 : FAST
72
C 72
External switch input RSW6
0
3 : G.SOAK is cleared using OR.
4 : G.SOAK is cleared using AND.
5 : MANUAL/AUTO
73
C 73
External switch input RSW7
0
6 : AT start /terminate
7 : PV1/PV2
8 : Auto load
74
C 74
External switch input RSW8
0
9 : PV1
→
PV2 standby
10: PV2
→
PV1 standby
11: NOP (does not function.)
12: Normal operation/reverse operation
75
C 75
External switch input RSW9 to 16 0
0 : BCD4 bit X 2 digits
(program selection)
1 : Binary 7 bits
76
C 76
Communication address
0
0 to 127
77
C 77
Transmission rate
0
0 : 9600bps
1 : 4800bps
2 : 2400bps
3 : 1200bps
78
C 78
Transmission code
0
0 : 8 bits, even parity, 1 stop bit
1 : 8 bits, no parity, 2 stop bits
79
C 79
Communication protocol
0
0 : CPL
1 : ST221 (no PV trend)
2 : ST221 (PV trend)
80
C 80
Communication method
0
0 : RS-485
1 : RS-232C
81
C 81
ROM ID
—
< Description >
82
C 82
ROM ITEM
—
Can only be referenced for mechanical service use.
83
C 83
ROM revision
—
84
C 84
Data version
—
85
C 85
CPU board ID
—
86
C 86
I/O board ID
—
90
C 90
PID type
1
0 : Improved
1 : Compatible with Mark
I
91
C 91
PV1 burnout
0
0 : Provided
1 : Not provided
92
C 92
PV2 burnout
0
0 : Provided
1 : Not provided
93
C 93
Time proportional output system 0
0 : Does not go on a second time off in time proportional cycle.
1 : Goes on a second time in time proportional cycle.
95
C 95
Voltage output tuning
15
2 to 22 mA
97
C 97
Communication port
0
0 to 15
Uses back plate terminal to setting 0.
Uses loader jack to setting 1 to 15.
98
C 98
Special function
0
0 to 255
99
C 99
PV1 zener barrier adjustment
—
–20.00 to +20.00
100
C100
PV2 zener barrier adjustment
—
–20.00 to +20.00
denotes items settable only on models with two PV input channels.
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...