Chapter 11. SPECIFICATIONS
Item
Specifications
Mode
Control section
Output section
Program run mode
READY
RUN
HOLD
FAST
END
READY FAST
Proportional band (P)
PID control
0.0 to 1000.0% (0.0: On-off control)
Integral time (I)
0 to 3600s (0: PD control)
Derivative time (D)
0 to 1200s (0: PI control)
Manipulated variable
limit
Low-limit
: –5.0% to high-limit
High-limit : Low-limit to +105.0%
Manual reset
0.0 to 100.0%
Programmer function
Auxiliary output
Auto tuning
Automatic setting of PID value by limit cycle method
Manipulated variable change 0.1 to 110.0%/0.1s
On-off control differential
0 to 1000U
Scaling
Possible
Scaling
Possible
Selection
Manipulated variable output is selectable to SP output
Type
PV, SP, deviation, MV, PV1, PV2
Output resolution
1/10000
PID groups selection
Segment specified, automatic zone selectable during
program run
No. of PID groups
16 groups for program operation (9 segment specific
and 7 automatic zone selecting)
Constant value control
mode
READY
: Preparation state (control stop)
RUN : Run state
AUTO : Automatic run state
MANUAL : Manual run state (output is operatable to console)
AUTO
: Automatic run state
MANUAL
: Manual run state (Enables manual output from system console.)
Normal reverse operation selection
Selection is settable
Current output (5G)
Auxiliary output CH1, CH2
Output current
Allowable load resistance
Output accuracy
Output resolution
Max. output current
Min. output current
Output update cycle
Open time terminal voltage
: Preparation state (control stop, select of program number is possible.)
: Advancing run state
: Hold run state
: Fast feed run state
: End point run state
: Preparation and the fast feed state
: 4 to 20mA dc
: Lower than 600 (under operating conditions)
: Lower than 0.1% FS (under the standard conditions)
: 1/10000
: 21.6mA dc
: 2.4mA dc
: 0.1s
: Lower than 25V
11-3
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...