Chapter 7. PARAMETER SETUP
■
Constant value control data setting
0: Program run mode
1: Constant value control mode
[Description:]
When setup
C21
is set to 0, this setting is automatically
set to 0.
0
ConSt
1
Control mode
Within the range of setup
C66
to
C67
(SP limit)
0
SP
2
Setpoint
0.0 to 1000.0%
A setting of 0.0 turns on ON-OFF control
100.0
P
3
Proportional band
0 to 3600sec
No integral operation when set to 0.
[Description:]
When
P
is set to 0.0, Ò-----Ó is displayed and setting cannot be performed.
0
I
4
Integral time
0 to 1200 sec
No integral operation when set to 0.
[Description:]
When
P
is set to 0.0, Ò-----Ó is displayed and setting cannot be performed.
0
d
5
Derivative time
0.0 to 100.0%
[Description:]
When
P
is set to 0.0, Ò-----Ó is displayed and setting cannot be
performed.When I is not equal to 0, Ò-----Ó is displayed and
setting cannot be performed.
50.0
rE
6
Manual reset
Ð5.0% to upper limit
0.0
oL
7
Manipulated variable lower limit
Lower limit to +105%
100.0
oH
8
Manipulated variable upper limit
7-34
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...