11
DCP551 Parameter Work Sheet
No.
Item code
Item
Factory default
-
User
Settings and descriptions
settings
settings
1
C 01
PV1 range number
0
0 to 16
: Thermocouple
48 to 52
: Linear (DC current and DC voltage)
64 to 71
: Resistance temperature detector
96 to 103 : Resistance temperature detector
128 to 134: Linear (DC current and DC voltage)
2
C 02
PV1 temperature unit
0
0 : Celsius (
°
C)
1 : Fahrenheit (
°
F)
3
C 03
PV1 decimal point position
1
0 to 2
4
C 04
PV1 linear decimal point position 1
0 to 4
5
C 05
PV1 linear range lower limit
0 PVU
–19999 to +20000 PVU(PV1)
6
C 06
PV1 linear range upper limit
10000 PVU
–19999 to +20000 PVU(PV1)
7
C 07
PV1 cold junction compensation
0
0 : Provided (Compensated inside the instrument)
1 : Not provided (Compensated outside the instrument)
8
C 08
PV1 root extraction
0
0 : Not provided
1 : Provided
9
C 09
PV1 root extraction dropout
0.2
0.2 to 10.0% (Ratio to input range)
10
C 10
PV1 cold junction bias
0.0
–1.0 to + 1.0
°
C
11
C 11
PV2 range number
0
0 to 16
: Thermocouple
48 to 52
: Linear (DC current and DC voltage)
64 to 71
: Resistance temperature detector
96 to 103 : Resistance temperature detector
128 to 134: Linear (DC current and DC voltage)
12
C 12
PV2 temperature unit
0
0 : Celsius (
°
C)
1 : Fahrenheit (
°
F)
13
C 13
PV2 decimal point position
1
0 to 2
14
C 14
PV2 linear decimal point position 1
0 to 4
15
C 15
PV2 linear range lower limit
0 PVU
–19999 to +20000 PVU(PV2)
16
C 16
PV2 linear range upper limit
10000 PVU
–19999 to +20000 PVU(PV2)
17
C 17
PV2 cold junction compensation
0
0 : Provided (Compensated inside the instrument)
1 : Not provided (Compensated outside the instrument)
18
C 18
PV2 root extraction
0
0 : Not provided
1 : Provided
19
C 19
PV2 root extraction dropout
0.2
0.2 to 10.0% (Ratio to input range)
20
C 20
PV2 cold junction bias
0.0
–1.0 to + 1.0
°
C
21
C 21
Control output system
1
0 : 5S output (Current proportional SP output)
1 : 5G output (Current proportional control output)
2 : 6D output (Voltage time proportional control output) system A
3 : 6D output (Voltage time proportional control output) system B
4 : 8D output (open collector time proportional control output) system A
5 : 8D output (open collector time proportional control output) system B
23
C 23
Control action
0
0 : PID — A reverse operation
1 : PID — A normal operation
2 : PID — B reverse operation
3 : PID — B normal operation
25
C 25
PV channel switching type
0
0 : PV1 low-temperature sensor, PV2 high-temperature sensor
1 : PV1 high-temperature sensor, PV2 low-temperature sensor
2 : PV1 tied
3 : PV2 tied
4 : Backup switching
26
C 26
PV channel switching system
0
0 : External switch switching
1 : Automatic switching (swi dead band)
2 :
Automatic switching B (swi dead band + external switch)
3 : Automatic switching C (2-point proportional)
27
C 27
PV channel switching point
10000 PVU
–19999 to +20000 PVU(PV1)
28
C 28
PV channel switching dead band 100 PVU
1 to 1000 PVU(PV1)
■
Setup data setting
denotes items settable only on models with two PV input channels.
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...