Chapter 5. FUNCTIONS
■
PV start
When a PV start is set in the program setting, a PV start is performed in a normal RUN
operation.
The program looks for the first point where PV and the program pattern SP are equal
(both PV and SP include bias) and starts operation from there. PV starts are of three
kinds: rising PV start that looks for a point where PV and SP are equal on a rising
RAMP, falling PV start that looks for a point where PV and SP are equal on a falling
RAMP and bi-directional PV start that looks for such a point both on rising and falling
RAMPs.
Note, however, that if there is no point where PV and SP are equal, operation starts from
the beginning of segment 1.
When a PV start has been implemented, the event operating point and the time event
time are automatically corrected. This is described in the figure shown below. When PV
is at (1) in the figure, a rising PV start or a bi-directional PV start starts from B and a
falling PV start starts from C. When PV is at (2) in the figure, a falling PV start or a bi-
directional PV start starts from D and a rising PV start starts from A. When PV is at (3)
in the figure, any PV start starts from A.
NOTE
PV start is valid for segments in the selected program but not for segments beyond a pat-
tern link destination.
5-20
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...