Chapter 7. PARAMETER SETUP
0 : 5S output (current proportional SP output)
1 : 5G output (current proportional control output)
2 : 6D output (voltage time proportional control output) system A
3 : 6D output (voltage time proportional control output) system B
4 : 8D output (open collector time proportional control output) system A
5 : 8D output (open collector time proportional control output) system B
[Description:]
The difference between system A and system Bis in the output system of
ON-OFF control and auto-tuning.
System A: Output ON-OFF is performed regardless of time proportional
output cycles and output limits.
System B: The output limit upper limit value is output instead of on and the
output limit lower value is output instead of off according to time
proportional output cycles.
1
C 21
21
Control output system
[Description:]
----- is displayed and setting cannot be performed.
----
C 22
22
Unused
----
C 24
24
Unused
0: External switch switching
1: Automatic switching A (swi dead band)
2: Automatic switching B(swi dead band +
external switch)
3: Automatic switching C (2-point proportional)
[Description:]
----- is displayed and setting cannot be performed on
model with one PV input channel.
When
C25
is set to more than 1, [----] is displayed and
setting cannot be performed.
0
C 26
26
PV channel switching system
Ð19999 to +20000 PVU (PV1)
[Description:]
----- is displayed and setting cannot be performed on model
with one PV input channel.
When
C25
is set to more than 1, ----- is displayed and setting
cannot be performed.
When
C26
is set 0, ----- is displayed and setting cannot be
10000PVU
C 27
27
PV channel switching point
0: PID-A reverse operation
1: PID-A normal operation
2: PID-Breverse operation
3: PID-Bnormal operation
[Description:]
PID-A: deviation derivative PID (system where SP
changes are affected by derivative action)
PID-B: derivative-based PID (system where SP changes
are not affected by derivative action)
0
C 23
23
Control operation
0: PV1 low-temperature sensor, PV2 high-temperature
sensor
1: PV1 high-temperature sensor, PV2 low-temperature
sensor
2: PV1 tied
3: PV2 tied
4: Backup switching
[Description:]
----- is displayed and setting cannot be performed on
model with one PV input channel.
0
C 25
25
PV channel switching type
D
+
SP
P
I
MV
PV
D
+
SP
P
I
MV
PV
7-23
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...