Chapter 8. PROGRAM SETUP
■
Setting PV shift items
(1) In the set value display state, move to the PV shift item to be set for the segment on
the programming map.
(2) Press the
ENTER key
to make display panel 2 flash (registration of first setting).
(3) Use the
↑
,
↓
,
←
, and
→
keys
to make the first setting – setting the PV shift set
value.
Setting range: –10000 to +10000 SPU
(4) Press the
ENTER key
to stop the flashing on display panel 2.
(Pressing the
FUNC
and
CLR keys
causes display panel 1 to return to unset state
“-----” and the flashing stops.)
●
Display
• Unset values are indicated as “-----”.
• When setup data
C59
is set to 1, a PV shift item on the programming map is skipped
and not displayed.
NOTE
PV shift uses a subfunction. A subfunction cannot be used when a setting has not been
made “-----”.
HANDLING PRECAUTIONS
• When PV shift is not set, it is a sequel to a PV shift value in a previous seg-
ment. When PV shift is not set in the first segment, the set value is 0.
P V S H I F T
8-14
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...