Chapter 10. TROUBLESHOOTING
●
Autotuning cannot be canceled with
AT key
●
PID parameter setting state cannot be invoked with
PID key
●
Event configuration setting state cannot be invoked with
FUNC
and
PARA keys
●
Setup data setting state cannot be invoked with
SETUP key
●
Constant value control data setting state cannot be invoked with
FUNC
and
PID keys
●
Program setting state cannot be invoked with
FUNC
and
PROG keys
●
Program copy cannot be performed with
↑
and
PROG keys
Set to be except READY mode.
Set READY mode to execute RESET operation (
).
Program selected in READY mode is unset.
Select number of a set program.
Constant value control mode is on.
Set constant value control data
ConSt
to 0.
Mode other than READY
Press to invoke normal display mode.
Program protected
Set variable parameter
PA02
to 0, 2 or 4.
Set to key lock.
Set variable parameter
PA01
to 0.
ConSt
PA01
!
"
PA01
"# $ %
!
"
PA01
"# $ %
PA01
Cause
Measure
Set to key lock.
Set variable parameter
PA01
between 0 to 2.
10-5
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...