Chapter 5. FUNCTIONS
■
PID group selection
• PID groups can be selected in two ways: by setting a PID segment or through auto-
matic PID group switching.
A PID group segment and automatic PID group switching can also be combined.
When a PID group number is set to 0, the setting in the previous segment is continued.
• In a PID group segment setting a PID group number is set in each segment and PID
parameters are used for calculating the control output. The nine PID groups
PID1
to
PID9
can be used.
• In automatic PID group switching, the entire SP scale is divided into seven zones
assigning
CP-A1
to
CP-A6
to each. The PID constants that are used according to SP
values are automatically selected to calculate control output. The PID group number
for each segment specifies A. Seven PID groups from
PID-A1
to
PID-A7
can be
used.
■
Selection of ouput limiter group
• Output limiter group number can be set for each segment to control the lower limit
(OL) and upper limit (OH) of the control output.
oL
and
oH
groups 1 to 9 can be used.
• The output limiter can only be specified by segment; automatic selection cannot be
made.
• When the output limiter is set to 0, the setting in the previous segment is continued.
!
CP-A6
CP-A5
CP-A4
CP-A3
CP-A2
CP-A1
PID group number
1
2
3
4
PID group segment setting
5-16
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...