Chapter 12. CALIBRATION
■
Cold junction sensor calibration
Scroll
↑
,
↓
,
←
, or
→
keys
to show (
2022
) on upper display, then press
ENTER key
.
●
The cold junction input 0% (CH1)
(1) Press
SETUP key
until the PROG/SEG display shows (
02-01
).
(2) Connect the millivolt source between (55)(–) and (56)(+), and then input 0.2V (See
Figure 12-10).
(3) Press
ENTER key
after display stabilizes, AD count is shown on lower display.
●
The cold junction input 100% (CH1)
(1) Press
SETUP key
until the PROG/SEG display shows (
02-02
).
(2) Connect the millivolt source between (55)(–) and (56)(+), and then input 1.0V (See
Figure 12-10).
(3) Press
ENTER key
after display stabilizes, AD count is shown on lower display.
●
The cold junction AD count data (CH1)
(1) Press
SETUP key
until the PROG/SEG display shows (
02-03
).
(2) Press
ENTER key
after display stabilizes, AD count is shown on lower display.
●
The cold junction temperature data (CH1)
(1) Press
SETUP key
until the PROG/SEG display shows (
02-04
).
(2) Connect the thermometer (55).
(3) Scroll
↑
,
↓
,
←
, or
→
keys
to set above temperature value.
(4) Press
ENTER key.
●
The cold junction input 0% (CH2)
(1) Press
SETUP key
until the PROG/SEG display shows (
02-05
).
(2) Connect the millivolt source between (58)(–) and (59)(+), and then input 0.2V (See
Figure 12-10).
(3) Press
ENTER key
after display stabilizes, AD count is shown on lower display.
●
The cold junction input 100% (CH2)
(1) Press
SETUP key
until the PROG/SEG display shows (
02-06
).
(2) Connect the millivolt source between (58)(–) and (59)(+), and then input 1.0V (See
Figure 12-10).
(3) Press
ENTER key
after display stabilizes, AD count is shown on lower display.
●
The cold junction AD count data (CH2)
(1) Press
SETUP key
until the PROG/SEG display shows (
02-07
).
(2) Press
ENTER key
after display stabilizes, AD count is shown on lower display.
●
The cold junction temperature data (CH2)
(1) Press
SETUP key
until the PROG/SEG display shows (
02-08
).
(2) Connect the thermometer (58).
(3) Scroll
↑
,
↓
,
←
, or
→
keys
to set above temperature value.
(4) Press
ENTER key.
●
Writing into EEPROM
(1) Press
SETUP key
until the PROG/SEG display shows (
02-09
).
(2) Scroll
↑
,
↓
,
←
, or
→
keys
to show (
1.1.1.1.
) on upper display.
(3) Press
ENTER key.
12-14
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...