DCP551 Parameter Work Sheet
denotes items settable only on models with two PV input channels.
No.
Item code
Item
Factory default
-
User
Settings and descriptions
settings
settings
29
C 29
Selections available when power
0
0 : Continues until power is turned off.
is on during PV channel switching
1 : PV1
2 : PV2
3 : High-temperature PV
4 : Low-temperature PV
30
C 30
PV equalizer
0
0 : Not provided
1 : PV1 only
2 : PV2 only
3 : Both PV1 and PV2
31
C 31
End of operation
0
0 : READY mode
1 : END mode
32
C 32
Manipulated variable in READY mode 0.0
–5.0 to +105.0%
33
C 33
Manipulated variable setting
0
0 : Not provided
in PV overrange
1 : Provided
34
C 34
Manipulated variable in PV
0.0
–5.0 to +105.0%
overrange
35
C 35
MANUAL change mode
0
0 : Smooth
1 : Preset
36
C 36
Preset MANUAL value
0.0
–5.0 to +105.0%
43
C 43
Service interruption time when running can be continued
0
0 to 3600sec
45
C 45
Auxiliary output 1 type
0
0 : SP
1 : PV
2 : Deviation (DEV)
3 : Manipulated variable (MV)
4 : PV1
5 : PV2
46
C 46
Auxiliary output 1 lower limit (4mA) 0 SPU
–19999 to +20000 SPU (
C45
not equal to 3)
–1999.9 to +2000.0% (
C45
set to 3)
47
C 47
Auxiliary output 1 upper limit (20mA) 10000 SPU
–19999 to +20000 SPU (
C45
not equal to 3)
–1999.9 to +2000.0% (
C45
set to 3)
48
C 48
Auxiliary output 2 type
0
0 : SP
1 : PV
2 : Deviation (DEV)
3 : Manipulated variable (MV)
4 : PV1
5 : PV2
49
C 49
Auxiliary output 2 lower limit (4mA) 0 SPU
–19999 to +20000 SPU (
C48
not equal to 3)
–1999.9 to +2000.0% (
C48
set to 3)
50
C 50
Auxiliary output 2 upper limit (20mA) 10000 SPU
–19999 to +20000 SPU (
C48
not equal to 3)
–1999.9 to +2000.0% (
C48
set to 3)
52
C 52
SP output lower limit (4mA)
0 SPU
–19999 to +20000 SPU
53
C 53
SP output upper limit (20mA)
10000 SPU
–19999 to +20000 SPU
57
C 57
Programming item
0
0 : Displayed
Event
1 : Not displayed
58
C 58
Programming item
0
0 : Displayed
PID group, output limiter group
1 : Not displayed
59
C 59
Programming item
0
0 : Displayed
G.SOAK, PV shift, repeat
1 : Not displayed
60
C 60
Programming item
0
0 : Displayed
PV start, cycle, pattern link
1 : Not displayed
61
C 61
Programming system
0
0 : RAMP-X and RAMP-T (
θ
) combined
1 : RAMP-X and RAMP-E (
∆
SP) combined
62
C 62
Program time unit
0
0 : Hours, min (SPU/hour for RAMP-T)
1 : Min, sec (SPU/min for RAMP-T)
2 : 0.1 sec (SPU/sec for RAMP-T)
63
C 63
Time display (display panel 2)
0
0 : Remaining segment time
1 : total operation time (after READY
→
RUN start)
65
C 65
SP decimal point position
1
0 to 4
Содержание DCP550
Страница 1: ...EN1I 6186 Issue 13 04 08 DCP551 Mark ΙΙ Digital Control Programmer User s Manual www honeyvell energy ...
Страница 115: ...Chapter 7 PARAMETER SETUP Settings by event type For information on event operations see Events pages 5 5 to 5 15 7 13 ...
Страница 117: ...Chapter 7 PARAMETER SETUP 0 1 02 3 02 3 0 1 1 4 5 1 4 6 1 4 5 2 2 2 7 15 ...
Страница 119: ...Chapter 7 PARAMETER SETUP 0 11 2 2 3 3 7 17 ...
Страница 122: ...Chapter 7 PARAMETER SETUP d A5 tP A5 CP A5 rE A5 P A6 I A6 d A6 rE A6 CP A6 tP A6 P A7 I A7 d A7 rE A7 CP A7 tP A7 7 20 ...
Страница 209: ...Chapter 12 CALIBRATION Figure 12 11 Current Outputs 12 18 ...
Страница 229: ......
Страница 230: ...No CP UM 5024E ...