Windsor 500 Programming Manual - Issue C
- 56 -
System reset menu
230v Flt
This option affects the response to a mains failure. Normally (option off) the mains must be off
for the 230v Delay programmable period (default is 5 minutes) before a mains failure is
recognised by the panel. If the 230v fault option is on then a mains failure will be recognised
after a delay of 30 seconds. If this option is on and the mains is off then the message “230v
Failed” will be displayed on all keypads which are not in use.
System reset menu
230v Warn.
The normal response for a mains fail includes an audible warning. The audible warning can be
disabled.
System Rst
230v Warn.-Off
On/Off
System reset menu
230v Delay
The delay before a mains fail is recognised is programmable. This option will be ignored if the
230v Flt option is on.
System Rst
230v Delay-005
1-255 minutes
System reset menu
Alarm Abort
The panel can be programmed to signal an alarm abort. If the user logs on within the
programmed abort period following an engineer resetable alarm event then an abort message
will be transmitted. An alarm abort can be transmitted in Ademco, point ID and Guardall
formats. Enter an abort time of 0 to disable this feature.
System Rst
Alarm Abort-0
0-255 seconds
Reset menu
Areas
Eng NA-Off
Eng PA-Off
Eng Tam-Off
New in v3.00
Auto Rst-Off
Strobe-Unset
Bank Rst-Off
Area reset menu
Eng Rst
You can select Engineer reset to apply to NA, PA and tamper type alarms. When Windsor is
configured for engineer reset and an engineer resetable alarm occurs, the user will be
prompted to call the engineer. The user can still reset in the normal way but is prevented from
setting the effected area. NA engineer reset applies to entry alarms and NA, ER and 24Hr
circuits. PA engineer reset applies to PA circuits and duress alarms. Tamper engineer reset
applies to all types of tamper The engineer prompt is;
Tel:031-333-2900
The top line will show the programmed service number.
Ref:123456
The bottom line will show the programmed site ID.