Windsor 500 Programming Manual - Issue C
- 37 -
Cct Type
Aux
Aux types can be configured for a set and/or an unset response. If an auxiliary circuit alarms
the event is logged in the event log as "Alarm". The programmed TX output is activated for
the programmed time (0-255 seconds). If 0 seconds is programmed for both the on time and
the delay time then the programmed output follows the state of the alarm input in real time.
Auxiliary circuit types can be programmed with a programmable delay period. When
alarmed the response is delayed for 0-255 seconds. Following the delay period the
response is the same as a non-delayed auxiliary type.
Aux
Help menu
Area 1-Off
On/Off
. . .
Area 7-Off
On/Off
TX-0
0-8
Dev-01
00-19
Gp1-Off
On/Off
. . .
Gp6-Off
On/Off
TX On Time-030
000-255 seconds
TX Delay-000
000-255 seconds
Set-On
On/Off
Unset-Off
On/Off
Slave Cct-0
0-max ccts
Tech-Off
On/Off
Dual-Off
On/Off
Log-On
On/Off
Cct Type
Shunt
Master shunt circuits can be programmed with a set and/or an unset response. When a
master shunt circuit alarms it will shunt all circuits in it’s programmed group and area (slave
circuits). If a slave circuit is programmed in more than 1 area it will be shunted if the master
shunt is programmed for any of the slave circuit areas. Windsor will ignore alarms from
shunted circuits.
The programmed master shunt TX output will be activated only if the master shunt circuit
clears and a circuit in the shunted group is active. Active circuits will remain shunted. The
programmed shunt TX output will only be turned off if the master shunt circuit changes state
from alarm to clear and all circuits in the programmed shunt group are clear. The master
shunt TX output would normally be used to indicate a fault condition. All shunt operations are
logged in the event log as "Shunt On" or Shunt Off".
Shunt
Help menu
Area 1-Off
On/Off
. . .
Area 7-Off
On/Off
TX-0
0-8
Dev-01
00-19
Shnt Group-1
1-6
Slave Cct-0
0-max ccts
Set-On
On/Off
Unset-Off
On/Off
Log-On
On/Off