Windsor 500 Programming Manual - Issue C
- 32 -
Edit page 2
Cct
All circuits are identified by the circuit number, 1 to 128. The programming options for each
circuit will depend on the programmed type. To view or modify a circuit configuration select
option 2 from page 2 of the edit menus followed by the circuit number. The circuit text
descriptor will be displayed for a few seconds and then the circuit configuration will be
displayed.
In version 3.00 the number of circuit types has been reduced but the number of circuit options
has been increased. Refer to the circuit options section for full details.
Cct menu
Type
Cct-001
Off
Help menu
0=Off
There are 2 pages of circuit types
1=NA
2=ER
3=EnEx
4=PB
5=24h
6=PA
7=Fire
8=Exc-D
9=Exc-T
↵
=Next Page
1=Aux
This help page can only be viewed by pressing help followed by
↵
2=Shunt
3=Eng Rst
4=Area Rst
5=PA-Snd
6=Key
7=Log On
↵
=Next Page
Each circuit type has a set of defaults which are loaded automatically when the type is
selected.
Cct Type
NA or ER
The only differences between the NA and ER response are;
•
an ER circuit is ignored during the entry sequence. This means that pre-warning
does not apply to ER type circuits.
•
an ER circuit alarm does not cause the programmed power reset outputs to be
activated during a reset.
NA and ER circuits can be programmed with an individual TX response however, NA and ER
alarms will also trigger the programmed set area alarm channel (see Comms/TX/Area n).