Windsor 500 Programming Manual - Issue C
- 45 -
Edit page 2
KP
Windsor can have up to 8 keypads connected on the keypad bus and an engineer keypad
connected directly to the main PCB. The keypads can be either an LCD keypad, a keypoint or
an INOVA Cardpoint. Windsor automatically detects the UI type at power up. Each keypad
can be individually programmed and LCD keypads can be programmed for different setting
modes on each area. To view or modify the keypad options select option 3 from page 2 of the
edit menus and then enter the keypad number.
1=Options
New in v3.00
2=EKP Set Mode
3=KP Set Mode
4=Logon TX
New in v3.00
5=LogOn/Unset
New in v3.00
KP menu
Options
Keypad-1
Type-Keypad
Help menu
Bleeper-Off
On/Off
Set Disp-Off
On/Off
PIN Attempts-3
0-99
PA Function-Off
On/Off
UI PA Sndr-Off
On/Off
Dual PIN-Off
On/Off
KP Options menu
Type
A keypad can be programmed as one of 3 different types.
0=Keypad
An LCD keypad
1=Keypoint
A keypoint
2=CardPoint
An INOVA Cardpoint
KP Options menu
Bleeper
Each keypad can be programmed for an audible response. Audible feedback for key presses
and faults will always be sounded but alarms and entry/exit tones will only be sounded if the
keypad bleeper option is on.
KP Options menu
Set Disp
Each LCD keypad can be programmed to indicate the set areas.
Set:14
Areas 1 and 4 are currently set.
Enter-
Even if a keypad is programmed for set display indication Windsor will not display the
set status unless the user has selected this format. The display format for the top line is
controlled using the
↑
button and bottom line by the
↓
button.