Windsor 500 Programming Manual - Issue C
- 28 -
Edit page 2
Conc
All circuits in a Windsor system are connected to an internal or external concentrator. All
concentrator types have 8 circuit inputs. Up to 16 concentrators may be connected which gives
Windsor a maximum circuit capacity of 128 circuits. Internal and external concentrators can be
used in any combination in a Windsor system. Three types of concentrator may be connected.
Concentrator Type
Internal
External
EOL (End of Line)
✓
✓
NEOL (No end of Line)
✓
✓
HS EOL ( High Security [HS] end of line)
✗
✓
Each concentrator has eight input circuits which are individually identified by Windsor. The
input circuit states recognised by Windsor are dependant on the concentrator type.
Type
Circuit States
EOL ,HS
Clear, Alarm, Tamper
NEOL
Clear, Alarm, Tamper, Alarm + Tamper
The minimum circuit response time is approximately 200mS. The actual response time will
depend on the number of configured concentrators, the concentrator type and when the circuit
alarm takes place relative to the circuit clock period on the synchronous concentrator bus.
Concentrator Type
Response Time < 8 Conc.
Response Time > 8 Conc.
External EOL
200-400mS
400-800mS
External NEOL
400-600mS
800-1200mS
External HS
200-400mS
400-800mS
Internal EOL or NEOL
200-400mS
400-800mS
External NEOL concentrators should not be used on systems with more than 8
concentrators if compliance with BS4737 is required.
If an internal and external concentrator with the same address are connected the
external concentrator inputs are ignored. More than one concentrator can be set to the
same address if the data line is not connected. This can be used, in conjunction with
fitted daughter boards, to build a mimic panel indicating the alarm status of all circuits.
Concentrator menu
Type
To view or modify a concentrator configuration select option 1 from page 2 of the edit menus
and then enter the concentrator number.
1=Type
There are 2 concentrator menu options.
2=Outputs
Conc-01 Type
EOL
Help menu
1=EOL
There are 4 types of concentrator.
2=NEOL-1
3=NEOL-2
4=HS