DVP-15MC Series Motion Controller Operation Manual
12-16
12
1
ErrorID
Meaning
How to deal with
Hex
Decimal
is out of the allowed area.
(%QX0.0~%QX127.7,%MX0.0~%
MX65535.7)
9030
36912
Object type error
Modify the value of the input parameter
ObjType.
9031
36913
The specified function code for
data reading exceeds the allowed
range.
Specify a new function code which is within
the allowed range.
9040
36928
The local buffer for data sending
has no enough space to meet the
specified length of data.
(%MW0~%MW32767)
Modify the start address of the local buffer or
specified data length.
9042
36930
The start address of the local
buffer for data sending is out of
the allowed word register area.
(Valid range:
%MW0~%MW32767)
Modify the start address of the local buffer.
9043
36931
The local buffer specified for data
receiving has no enough space to
meet the specified length of data.
(%MW0~%MW32767)
Modify the start address of the local buffer or
specified data length.
9045
36933
The start address of the local
buffer specified for data receiving
is out of the allowed word register
area.
(Valid range:
%MW0~%MW32767)
Modify the start address of the local buffer.
9100
37120
Socket instruction parameter
value exceeds the allowed range.
Modify the Socket instruction parameter
values within the allowed range.
9101
37121
Ethernet physical connection is
disconnected.
Check if the network cable connection is
proper.
9102
37122
TCP remote IP address error
Modify the setting for the remote IP address.
9103
37123
TCP port error
Modify the remote port setting.
9105
37125
An error occurs in the register
addresses for TCP data sending.
Modify register address for sending TCP
data.
9106
37126
TCP/UDP data receiving is in
process.
The last data receiving has not been
completed and thus the new receiving can
not be triggered.
9107
37127
TCP receiving register address
error
Modify the register address for receiving
TCP data.
9108
37128
The length of received data
exceeds the set length in TCP
server mode.
Set the length of received data to the length
which is greater than or equal to the number
of bytes of the first received data.
9109
37129
The length of received data
exceeds the set length in UDP
trasmission.
Set the length of received data to the length
which is greater than or equal to the number
of bytes of the first piece of received data.
910A
37130
UDP remote IP address error
Modify the remote IP address setting.
910B
37131
UDP port error
Local port and remote port can not be 0 at
the same time.
910C
37132
An error occurs in the register
addresses for sent UDP data.
Modify the register addresses for sent data.
910D
37133
An error occurs in the register
addresses for received UDP data.
Modify the register addresses for storing the
received data.
Содержание DVP-15MC Series
Страница 16: ...1 1 1 Preface Table of Contents 1 1 Explanation of Symbols in This Manual 1 2 1 2 Revision History 1 3...
Страница 19: ...DVP 15MC Series Motion Controller Operation Manual 1 4 _1 MEMO...
Страница 20: ...2 1 2 Overview Table of Contents 2 1 Product Description 2 2 2 2 Functions 2 2 2 3 Profile and Components 2 3...
Страница 23: ...DVP 15MC Series Operation Manual 2 4 _2 MEMO...
Страница 31: ...DVP 15MC Series Motion Controller Operation Manual 3 8 _3 MEMO...
Страница 75: ...DVP 15MC Series Motion Controller Operation Manual 6 26 _6 MEMO...
Страница 87: ...DVP 15MC Series Motion Controller Operation Manual 7 12 _7 MEMO...
Страница 432: ...Chapter 8 Logic Instructions 8 345 8_ MEMO...
Страница 433: ...9 1 9 Chapter 9 Introductions of Axis Parameters Table of Contents 9 1 Description of Axis Parameters 9 2...
Страница 470: ...DVP 15MC Series Motion Controller Operation Manual 10 34 10 MEMO...
Страница 878: ...DVP 15MC Series Motion Controller Operation Manual 11 408 11 1 MEMO...
Страница 920: ...DVP 15MC Series Motion Controller Operation Manual A 16 A MEMO...
Страница 941: ...D 1 D Explanation of Homing Modes Table of Contents D 1 Explanation of Homing Modes D 2...