DVP-15MC Series Motion Controller Operation Manual
12-14
12
1
ErrorID
Meaning
How to deal with
Hex
Decimal
Socket function are both 0.
function as a value which is not 0.
9010
36880
RS485 PLC Link number
exceeds the range of 1-24.
Modify PLC Link number as a value within
the range of 1-24.
9011
36881
The written-data length
configured for RS485 PLC link
exceeds the allowed maximum
value.
Modify written data length configured for
RS485 PLC link as a value which is within
the allowed range.
9012
36882
The read data length configured
for RS485 PLC link exceeds the
allowed maximum value.
Modify read data length configured for
RS485 PLC link as a value within the
allowed range.
9013
36883
The length of sent data
configured for RS485 free
protocol function exceeds the
allowed maximum value.
Modify the length of sent data configured for
RS485 free protocol function as a value
within the allowed range.
9014
36884
The length of received data
configured for RS485 free
protocol function exceeds the
allowed maximum value.
Modify the length of received data
configured for RS485 free protocol function
as a value within the allowed range.
9015
36885
The number of the RS232 PLC
Link exceeds the range of 1~24.
Modify the number of the RS232 PLC Link
as a value within the range of 1-24.
9016
36886
The written-data length
configured for RS232 PLC link
exceeds the allowed maximum
value.
Modify the written-data length configured for
RS232 PLC link as a value within the
allowed range.
9017
36887
The read-data length configured
for RS232 PLC link exceeds the
allowed maximum value.
Modify the read-data length configured for
RS232 PLC link as a value within the
allowed range.
9018
36888
The length of sent data
configured for RS232 free
protocol function exceeds the
allowed maximum value.
Modify the length of sent data configured for
RS232 free protocol function as a value
within the allowed range.
9019
36889
The length of received data
configured for RS232 free
protocol function exceeds the
allowed maximum value.
Modify the length of received data
configured for RS232 free protocol function
as a value within the allowed range.
901A
36890
Communication timeout time
setting in RS485/RS232 PLC link
configuration is improper.
Modify the timeout time as a value greater
than 0.
901B
36891
The lengths of read data and
written data configured for the
Ethernet/RS485/RS232 link are
both 0.
Modify either of the lengths of read data and
written data configured as a value which is
not 0.
901C
36892
The lengths of sent data and
received data configured for the
RS485/RS232 free protocol
function are both 0.
Modify either of the lengths of sent data and
received data configured as a value which is
not 0.
9020
36896
The local buffer of word type for
data writing has no enough space
to meet the specified length of
data.
(Valid range:
%MW0~%MW32767)
Modify the start address of the local buffer to
make it have enough space to meet the
specified data length.
9021
36897
The start address of the local
buffer of word type for data
Modify the start address of the local buffer
within the allowed word register area.
Содержание DVP-15MC Series
Страница 16: ...1 1 1 Preface Table of Contents 1 1 Explanation of Symbols in This Manual 1 2 1 2 Revision History 1 3...
Страница 19: ...DVP 15MC Series Motion Controller Operation Manual 1 4 _1 MEMO...
Страница 20: ...2 1 2 Overview Table of Contents 2 1 Product Description 2 2 2 2 Functions 2 2 2 3 Profile and Components 2 3...
Страница 23: ...DVP 15MC Series Operation Manual 2 4 _2 MEMO...
Страница 31: ...DVP 15MC Series Motion Controller Operation Manual 3 8 _3 MEMO...
Страница 75: ...DVP 15MC Series Motion Controller Operation Manual 6 26 _6 MEMO...
Страница 87: ...DVP 15MC Series Motion Controller Operation Manual 7 12 _7 MEMO...
Страница 432: ...Chapter 8 Logic Instructions 8 345 8_ MEMO...
Страница 433: ...9 1 9 Chapter 9 Introductions of Axis Parameters Table of Contents 9 1 Description of Axis Parameters 9 2...
Страница 470: ...DVP 15MC Series Motion Controller Operation Manual 10 34 10 MEMO...
Страница 878: ...DVP 15MC Series Motion Controller Operation Manual 11 408 11 1 MEMO...
Страница 920: ...DVP 15MC Series Motion Controller Operation Manual A 16 A MEMO...
Страница 941: ...D 1 D Explanation of Homing Modes Table of Contents D 1 Explanation of Homing Modes D 2...
Страница 966: ...DVP 15MC Series Motion Controller Operation Manual D 26 D MEMO...